Brand Name : SHAN CABLE

Model Number : WDZAN-YJY 0.6/1 KV CU/MICA/XLPE/LSOH

Certification : CE, IEC

Place of Origin : CHINA

MOQ : 500M

Price : 0.1-99 USD/M

Payment Terms : L/C, D/A, D/P, T/T

Supply Ability : 5000 KM/Month

Delivery Time : 10 working days

Packaging Details : Wooden Iron Drum

Conductor : Copper conductor

Insulation : XLPE

Wrapping tape : LSOH bending tape

Sheath : LSOH Sheath

Standards : IEC60332,IEC60502, IEC60228

Cores : 4

Corporation : shenghua group

Brand : Sh Cable

Contact Now

Application:
To be laid directly in ground, outdoors, indoors and in cable ducts.
Used for tall building, Hospital, Theatre, Power station, Metro Tunnel or Petrochemical Industry or other special place required for low smoke , zero halogen clean and safe cable.

Construction:

1 ..... stranded (RM) bare copper
2 ..... Mica Tape for Fire Resistant
3 ..... core insulation of cross-linked polyethylene
4 ..... Fillers
5 ..... Wrapping tape or Flame Retardant tape
6 ..... PVC Inner Bedding
7 ..... Galvanized Steel Wire Armour
8 ..... outer sheath of Low smoke halogen-free flame retardantmaterial (LSOH)

Standards:

IEC 60502, 60228, 60332, 60331
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Technical data:
Test voltage 0.6/1 kV [kV] 3.5 / 5 min.
Temperature range in motion -5°C till +70°C
fixed -20°C till +70°C
Operating temperature short circuit °C 250
Short circuit time max. [sec] 5
Bending radius min. x diameter 15
Flammability standard EN 60332-1-2

Specifications:

Nom. Cross-section of conductor

Strands
No./Dia. Of Conductor

Insulation ThicknessInner Covering ThicknessDia. Of Armor WireSheath ThicknessApprox. O.D.

Approx.
Weight

Max. D.C Resistance of Conductor (20 ℃)Testing Voltage A.CCurrent Rating
mm2pc/mmmm mm(mm)kg/kmΩ /kmkV/5minIn air (A)In soil(A)
4 × 47/0.850.71.00.91.818.06994.613.53445
4 × 67/1.040.71.01.251.819.08203.083.54357
4 × 107/1.380.71.01.251.822.012331.833.56077
4 × 167/1.780.71.01.61.824.515501.153.583105
4 × 257/2.140.91.01.61.829.220360.7273.5105125
4 × 357/2.520.91.02.01.932.525010.5243.5125155
4 × 5010/2.521.01.02.02.033.030640.3873.5160185
4 × 7014/2.521.11.02.02.137.039740.2683.5200225
4 × 9519/2.521.11.22.02.343.050320.1933.5245270
4 × 12024/2.521.21.22.52.545.063270.1533.5285310
4 × 15030/2.521.41.42.52.751.077650.1243.5325345
4 × 18537/2.521.61.42.52.856.092050.09913.5375390
4 × 24048/2.521.71.42.53.062.0114440.07543.5440450
4 × 30061/2.521.81.62.53.267.0138300.06013.5505515
4 × 40061/2.972.01.63.153.574.0196730.04703.5570575




Fireproof LSZH Low Smoke Zero Halogen Cable 4 Cores IEC 60228 / IEC 60332






































Product Tags:

low smoke zero halogen wire

      

lszh power cable

      
Best Fireproof LSZH Low Smoke Zero Halogen Cable 4 Cores IEC 60228 / IEC 60332 wholesale

Fireproof LSZH Low Smoke Zero Halogen Cable 4 Cores IEC 60228 / IEC 60332 Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Shanghai Shenghua Cable (Group) Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)